CONTACT US

EN1822 Width (mm) Height (mm) Depth (mm) Initial Pressure Drop (Pa) Air Flow (m3/hr)
H13 592 592 292 230 3400
H13 592 287 292 230 1500
H14 592 592 292 265 3400
H14 592 287 292 265 1500

Specification

Application

Hospitals, food processing, educational institute, pharmaceutical manufacturing, cleanroom, gas turbine intake systems

Filter Frame

Aluminium

Media

Micro Glass Fibre

Max Temperature (°C)

70°C

Recommended Final
Pressure Drop (Pa)

650

Related Products

Spectra Guard V-Bank

Spectra Guard V Bank has extended surface area and low pressure drop. These HEPA filters are designed for use in most commercial and industrial HVAC systems where medium to high efficiency filtration is required.

SPECTRA VX-TM

Spectra VX-TM has extended surface area and low pressure drop maintaining its efficiency from fine grade to HEPA range. These filters are designed for use in gas turbine systems where medium to high efficiency filtration is required. These filters are totally rigid making them ideal for variable air volume (VAV) systems, as well as applications downstream of supply fans. Application areas include gas turbine intake systems, high compressors and installations where safety and reliability are highly  required.